The value that the controller is aiming to achieve is called the:
Floating control may be used to control an analog device. The process will increase or decrease the control signal to the device based on its current position and its operating range. When floating control is used to control an analog device, the signal will be a value within a range, for example, between 0% and 100%. "
Which of the following are digital responses?
Two-position control always produces an analog response where the end device is either in an "on" state or “off†state. The controlled device is also analog.
What are the five control loop responses?
What is a differential and why are differentials needed in building controls?
A tri-state device can accept one of three input signals. What are the possible responses?
The difference between the actual value and the value that the controller is aiming to achieve is called the.
What is the throttling range?
Stability is achieved when the controller has obtained the desired value with zero offset.
We also review the terms associated with control loop responses, which included:
Read Also
- Set point
- Control point
- Offset
- Controlling variable
Floating control may be used to control an analog device. The process will increase or decrease the control signal to the device based on its current position and its operating range. When floating control is used to control an analog device, the signal will be a value within a range, for example, between 0% and 100%. "
- True
- False
Which of the following are digital responses?
- Proportional
- Proportional + Integral
- Proportional + Integral + Derivative
- All of the above
- None of the above
Two-position control always produces an analog response where the end device is either in an "on" state or “off†state. The controlled device is also analog.
- True
- False
What are the five control loop responses?
- Two-position response, floating response, proportional response, proportional plus integral, and proportional plus integral plus derivative response
- Two-position response, tri-state response, floating response, proportional response, and inverse response
- Tri-proportional response, integral response, derivative response, floating response and a programmed logic response
- None of the above
What is a differential and why are differentials needed in building controls?
- The differential is where the “deadband” or neutral zone occurs. It is needed to ensure the system differentiates between on and off.
- The differential is where the throttling range is maximized. Without a differential, the throttling range the actuator will hunt for the programmed logic, and not finding it, will eventually shut down.
- The differential is a characteristic of a two-position controller. It is the difference between the setting at which the controller operates at one position, and the setting at which it changes to the other position. This is needed to prevent the controller from rapidly cycling off and on, also known as “hunting”.
- None of the above
A tri-state device can accept one of three input signals. What are the possible responses?
- Clockwise rotation, counter-clockwise rotation, or remain stationary
- Open a contact, close a contact, or sound an alarm
- Increase proportional response, add integral response, add derivative response
- None of the above
The difference between the actual value and the value that the controller is aiming to achieve is called the.
- Error-Offset
- Differential
- Setpoint-Control point
- None of the above
What is the throttling range?
- The throttling range refers to the precision with which an actuator may be positioned, e.g. in increments of 10%
- The throttling range is the amount of change in the controlling variable required to run the actuator of the controlled device from one end of its stroke to the other end.
- The throttling range is the set of outputs that inversely correspond to the deadband of a floating response.
- None of the above
Stability is achieved when the controller has obtained the desired value with zero offset.
- True
- False
Summary of Building Controls III: Introduction to Control Loops Course
controllers are the components of the system that take in the data from the input devices, such as sensors or pushbuttons, and process them using programmed logic. The method with which the controller interacts with the controlled device is called the control loop response. We then identified the five control loop responses, which are:- A two-position response
- A floating response
- Proportional response (also called by its initial P)
- Proportional plus integral (or P.I.),
- Proportional plus integral plus derivative (also called P.I.D. response)
We also review the terms associated with control loop responses, which included:
- Set-point
- Offset or error—which is sometimes referred to as drift, deviation or control-point shift
- Stability
- Differential
- Neutral zone, and finally
- Throttling range
Read Also
- MCQ on Building Controls I: An Introduction to Building Controls | Primo Engineering
- MCQ on Building Controls II: Control Sensors | Primo Engineering
- MCQ on Building Controls III: Introduction to Control Loops | Primo Engineering
- MCQ on Building Controls IV: Two Position and Floating Responses | Primo Engineering
- MCQ on Measurement and Verification Including IPMVP Course
- MCQ on A Comparison of AC and DC Power Distribution in the Data Center Answer
- MCQ on HVAC Thermodynamic States | ENERGY UNIVERSITY COURSES
- تفاصيل مسابقة جامعة شنايدر للطاقة 2020 "Energy university championship "لطلاب هندسة كهربائية