1. Partial breakdown of winding insulation or due to overload on the supply system, this common problem known as -----
- a. None of these
- b. Overspeed
- c. Overcurrent
- d. Fallure of the prime-mover
- e. Failure of the field
Ans: c (Overcurrent)
2. Which tests are to be conducted to draw circuit diagram for a given induction motor? ((I. No Load test, II. Blocked rotor test, III. Running test, IV. Voltmeter-Ammeter test))
- a. I, II, III
- b. I, II, IV
- C. I, II
- d. I, II, III, IV
Ans: I, II(no load test and Blocked rotor test)
3. The magnitude of the unprotected zone of the generator stator winding depends upon the value of earthing resistance and relay setting. Select one:
- a.True
- b.False
Ans: True
4. At starting, developed mechanical torque is and developed power is
- a. not zero, zero
- b. zero, not zero
- c. not zero, maximum
- d. zero, zero
Ans : a (not zero, zero)
5. At starting, developed mechanical power is……. and developed torque is……
- a) zero, not zero
- b) zero, zero
- c) not zero, zero
- d) not zero, maximum
Ans: a(zero, notZero)
6. Three phase voltages are applied to the three windings of an electrical machine. If all supply terminal reversed, then the RMF wave......
- a. Direction remains same, amplitude unaltered
- b. Direction remains same, amplitude alters
- c. Direction reverses, amplitude alters
- d. Direction reverses, amplitude unaltered
Ans: a ( Direction remains same, amplitude unaltered)
7. If the stator winding fault is cleared quickly, it may lead to--------
- a.minimize the extent of damage.
- b.burning and welding-up of stator laminations.
- c.burning of stator coils. d. None of these.
Ans : a(minimize the extent of damage)
8. The field of each individual phase in rotating machines is
- a. None of the mentioned.
- b. a rotating magnetic filed RMF.
- c. not a rotating RMF but its amplitude pulsates.
- d. not a rotating RMF and its amplitude doesn't alternate.
Ans: c (not a rotating RMF but its amplitude pulsates.)
9. A 10kW,400V, 4-pole star connected induction motor gave the following test results: (( No load test: 400V, 8A, 250 W - Blocked rotor test: 90V,35A,1350 W)); The dc resistance is 0.6 ohms. The stator resistance is
- a. 0.6 ohms
- b. 0.9 ohms
- c. 1.2 ohms
- d. 0.4 ohms .
- e. 0.3 ohms
Ans: e (0.3 ohm)
10. If the stator winding fault is not cleared quickly, it may lead to
- (i) burning of stator coils
- (ii) burning and welding-up of stator laminations
- (iii) damage to other equipment
- (iv) all above
Ans: iv(all above)
11. The actual rotor resistance referred to the stator if the induction motor is
- a (r2)/s
- b. (r2)/(1-5)
- c (r2) (1-s)/s
- d. r2
Ans :d (r2)
12. The speed of RMF when a single phase supply is connected to the stator of three phase induction motor is
- a. -Ns
- b. zero
- c. 2NS
- d. Ns
Ans : b(zero)
13. The direction of rmf when a three phase supply is given to stator of three phase induction motor is?
- a) Zero
- b) Ns
- c) 2Ns
- d) –Ns
Ans : b(Ns)
14. The making/breaking circuit provides a command causing the appropriate circuit-breaker to disconnect. Select one:
a.True
b.False
Ans: TRUE
15. Unbalanced loading arises when a fault is ............
- I. Faults between phases and ground
- ii. None of these
- iii. Faults between phases
- iv. Faults to earth
- v. All of these
- vi. Three-phase faults
Ans : iii and iv ( Faults between phases and Faults to earth)
16. During no load test the wattmeter reading will be: ((I. stator copper loss, II. stator core loss, I rotor core loss , IV. friction and windage losses, V. Rotor copper loss ))
- a. ll, lll
- b. XI, IV
- C. I, II
- D. I, II, III
Ans: b(XI, IV)
17. The 3-phase IM is start and run as
- A. stat connected.
- B. delta connected
- C. delta then star respectively.
- D. star then delta respectively
Ans : D(star then delta)
18. The consequences of a sudden loss of all or the major part of the load on the alternator ......
- i. Failure of the prime-mover
- ii. Overspeed
- iii. Overcurrent
- iv. None of these
- V. Failure of the field
Ans : II (Overspeed)
19. star-commerte, 3-phase, OMVA, EG KV alternator has a perphase reactance of 10%. It is protected by Merz-Price a circulating-current principle that is set to operite for fault currents not less than 105 A. The value of carthing resistance to be provided in order to ensure that only 10% of the alternator winding remains unprotected is
- A. 2.171 ohm
- B. 2.159 ohm
- C. 2.059 ohm
- D. 2.176 ohm
- E. None of the above.
Ans : C( 2.059 ohm)
20. Three phase voltages are applied to the three windings of an electrical machine. If all supply terminals are reversed, then the RMF wave......
- a. Direction remains same, amplitude unaltered
- b. Direction remains same, amplitude alters
- c. Direction reverses, amplitude alters
- d. Direction reverses, amplitude unaltered
Ans : a (Direction remains same, amplitude unaltered)
21. A star-connected, 3-phase, 8MVA, 6.6 kV alternator has a per-phase reactance of 10%. It is protected by Merz-Price a circulating-current principle that is set to operate for fault currents not less than 195 A. The value of earthing resistance to be provided in order to ensure that only 10% of the alternator winding remains unprotected is .......
Ans : (1.9533 ohm)
22. External resistors method of induction motor starting, It cause
- a. Reduce motor terminal voltage
- b. Reduced efficiency
- C.all of the mentioned
- d. Reduce the current
Ans : c(all of the mentioned)
23. Full voltage starting of induction motor may cause
- a. dip in the voltages
- b. high voltage.
- c. high losses
- d. all of the mentioned
Ans : a(dip in the voltage)
24. The alternator runs as a synchronous motor and draws current from the supply system, These consequences are described as
- A. Failure of the prime-mover
- B. None of these
- C. Failure of the field
- D. Overcurrent
Ans : a( Failure of the prime-mover)
25. At standstill the equivalent of the 3-phase induction motor is similar to ___
- a) short-circuited two winding transformer.
- b) open circuit two winding transformer.
- c) stand still synchronous motor.
- d) none of the mentioned.
Ans : a(short-circuited two winding transformer)
26. Field failure of alternators needs to automatic protection against this contingency. Select one:
- a.True
- b.False
Ans : False
27. If the phase sequence of supply currents are reversed, then the direction of rotation of the 3 Phase IM wave will
- a. None of the mentioned
- b. Remains unchanged
- C. Cannot be determined
- d. Be reversed
Ans: d(Be reversed)
28. Overvoltage in an alternator occurs when speed of the primemover decreases due to sudden loss of the alternator load. Select one:
- a.True
- b.False
Ans : False
29. In the Merz-Price circulating scheme, the secondaries of each set of current transformers are connected in delta. Select one:
- a.True
- b.False
Ans : False
30) (I) Even at no load, a large 3-Ph IM must be started at reduced voltage. (11) If a large 3-Ph IM is started quickly at full voltage, it will be damaged. Is both statements (1), and (II) are false? Select one:
- A.True
- B.False
Ans: False
31) We do not require any protection against prime mover failure in case of
- A. Turbo generator sets
- B. Hydro generator sets
- C. Diesel engine driven alternators
- D. Back pressure turbo generators
Ans : a(Turbo generator sets)
32 ) Advantage of hydro-electric power station is Select one:
- a. Low operating cost
- b. Free from pollution problems
- c. No fuel transportation problems
- d. All of the above.
Ans: d (All of the above)
33) Short-circuit currents are due to……..
- A. single phase to ground faults
- B. phase to phase faults
- C. two phase to ground faults
- D. three phase faults
- E. any of these
Ans: E (any of these)
34) A 10kW,400V, 4-pole star connected induction motor gave the following test results: (( No-load test: 400V, 8A, 250 W -- Blocked rotor test: 90V,35A,1350 W )) ; The dc resistance is 0.6 ohms. The stator resistance is
35) The consequences of a sudden loss of all or the major part of the load on the alternator -----------
36) The actual rotor resistance referred to the stator if the induction motor is
- a. 1.2 ohms
- b. 0.4 ohms
- c. 0.6 ohms
- d. 0.9 ohms
- e. 0.3 ohms
35) The consequences of a sudden loss of all or the major part of the load on the alternator -----------
- i. Failure of the prime-mover
- ii. Failure of the field
- iii. None of these
- iv. Overspeed
- v. Overcurrent
- a. (r2)*(1-s)/s
- b. r2
- c. (r2)/s
- d. (r2)/(1-s)
37) The field of each individual phase in rotating machines is ......
- a. not a rotating RMF but its amplitude pulsates
- b. a rotating magnetic filed RMF
- c. None of the mentioned
- d. not a rotating RMF and its amplitude doesn’t alternate
38) If the phase sequence of supply currents are reversed, then the direction of rotation of the resultant MMF wave will ___________
51. The magnitude of the unprotected zone of the generator stator winding depends upon the value of earthing resistance and relay setting. Select one:
52. In the Modified Differential Protection for Alternators, the two-phase elements (PC and PA), and balancing resistance (BR) are connected in star. Select one:
53. As a 3-phase induction motor, as load increases from half load to full load, A. pf improves B. torque decreases C. slip decreases D. speed increases
54. For 3-phase induction motor, the characteristic of motor the torque .................with respect to slip.
55. The field of each individual phase inJotating machines is........ .
56. If the stator winding fault is cleared quickly, it may lead to-------
57. The consequences of a sudden loss of all or the major part of the load on the alternator -
58. The reverse power relay is used for.........
59. At standstill the equivalent of the 3-phase induction motor is similar to
60. Full voltage startingof induction motor may cause Not yet answered
61. 3-phase, 10 MVA, 6.2 kV alternator is protected by Merz Price circulating-current principle if the minimum fault current is 110A. The E.M.F induced in x% winding is (35.8x) volts. Select one:
62. The 3-phase IM is run as:
63. For 3-phase induction motor, as load increases from no load towards the full load,
64. A star-connected, 3-phase, 10 MVA, 6.6 kV alternator is protected by circulating current protection, the star point being earthed via a resistance (r). If 80% of the stator winding is protected against earth faults. Assume an earth fault setting of 20% of full-load current, and neglect the impedance of the alternator winding. Then the value of the earthing resistor is 9
65. If the three phase induction motor connected to a power grid with 3-delta connected capacitors draws a real positive power (P) and zero reactive power (Q). If the capacitors is reconnected to run with star-capacitors, then the motor will draw
66. During the blocked rotor test the wattmeter reading will be: (( I. stator copper loss , II. stator core loss, II. rotor core loss , IV. friction and windage losses, V. Rotor copper loss ))
67. The magnitude of the unprotected zone of the generator stator winding depends upon the value of earthing resistance and relay setting. Select one:
68. The calculated apparent impedance is compared with the reach point impedance. If the measured impedance is higher than the reach point impedance, it is assumed that a fault exists on the line between the relay and the reach point. Select one:
69. Buchholz relay is a gas-actuated relay installed in oil-immersed transformers for protection against all kinds of earth-faults. tot Select one:
70. In the Definite-Time Relays, the time of operation of each relay is fixed and is independent operating current. Select one:
71. A 3-phase transformer of 220/11.5kV line volts is connected in star/delta. The protective transformers on the 220 V side have a current ratio of 600/5. What should be the CT ratio on 11.5kV side?
72. Overvoltage in an alternator occurs when speed of the prime-mover decreases due to sudden loss of the alternator load. Select one:
73. The impedance of a transmission line is inversely proportional to its length, for distance measurement, it is appropriate to use a relay capable of measuring the impedance of a line up to a predetermined point (the reach point). Select one:
74. Protection against earth-faults in a transformer is Known as the core-balance leakage protection. Select one:
75. Overvoltage in an alternator oceurs when speed of the prime-mover decreases due to sudden loss of the alternator load. Select one:
76. Time-ordered protection of a radial feeder can be achieved by using (i) definite time relays and (ii) inverse time relays. Select one:
77. Overvoltage in an alternator occurs when speed of the prime-mover decreases due to sudden loss of the alternator load. Select one:
79. Overvoltage in an alternator occurs when speed of the prime-mover decreases due to sudden loss of the alternator load. utof Select one:
80. Unbalanced loading arises when a fault is
81. Overvoltage in an alternator occurs when speed of the prime-mover decreases due to sudden loss of the alternator load. Select one:
82. In the Merz-Price circulating scheme, the secondaries of each set of current transformers are connected in delta. Select one:
83. Overvoltage in an alternator occurs when speed of the prime-mover decreases due to sudden loss of the alternator load. of Select one:
84. If the neutral point of a star-connected the alternator is earthed through a low resistance, protection schemes will not provide sufficient sensitivity for earth-faults. of Select one:
85. 3-phase, 10 MVA, 6.6 kV alternator is protected by Merz Price circulating-current principle if the minimum fault current is 100A The EMF induced in x% winding is (39.1x) volts
89. For a delta/star power transformer, the CTs on the delta-side must be connected in delta and those on the star-side in the delta.Select one:
90. Field failure of alternators needs to automatic protection against this contingency Select one:
91. The basic principle of distance protection involves the division of the voltage at the relaying point by the measured current Select one:
- a) Be reversed
- b) Remains unchanged
- c) Cannot be determined
- d) None of the mentioned
39) When the rotor of a 3-phase induction motor is blocked, the slip is ……..
- zero
- 0.5
- 0.1
- 1
40) Partial breakdown of winding insulation or due to overload on the supply system, this common problem known as -------------
- i. Failure of the field
- ii. Overcurrent
- iii. Failure of the prime-mover
- iv. None of these
- v. Overspeed
41) At no-load, the rotor core loss of a 3-phase induction motor is ………
- large
- small
- practically zero
- none of the above
42) As a 3-phase induction motor, as load decreases from full load to half load, A. pf improves B. torque decreases C. slip decreases D. speed increases
- i. D only
- ii. B, C, D
- iii. A, B, D
- iv. A, B, C, D
- v. A only
43) If the neutral point of a star-connected the alternator is earthed through a low resistance, protection schemes will not provide sufficient sensitivity for earth-faults. Select one:
- True
- False
44) 3-phase, 10 MVA, 6.0 kV alternator is protected by Merz Price circulating-current principle if the minimum fault current is 120A. The E.M.F induced in x% winding is (33.641x) volts. Select one:
- True
- False
answer (false) and the correct phrase is
3-phase, 10 MVA, 6.0 kV alternator is protected by Merz Price circulating-current principle if the minimum fault current is 120A. The E.M.F induced in x% winding is (34.641x) volts.
46) Starting methods not applicable to both squirrel-cage and slip ring induction motors is/are: (( I. DOL starting , II. Auto transformer starting , III. Rotor resistance starting , IV. Stator resistance starting ))
- a. III
- b. I, II, III
- c. I, II, IV
- d. I, II
47) If the phase sequence of supply currents are reversed, then the direction of rotation of the 3-Phase IM wave will
- a. Cannot be determined
- b. Remains unchanged
- c. None of the mentioned
- d. Be reversed
48) If the three phase induction motor connected to a power grid with 3-star connected capacitors draws a real positive power (P) and zero reactive power (Q). If the capacitors is reconnected to run with delta-capacitors , then the motor will draw .............. (P) and ................. (Q).
- a. positive, negative
- b. positive, positive
- c. negative, negative
- d. negative, positive
49) Overvoltage in an alternator occurs when speed of the prime-mover decreases due to sudden loss of the alternator load. Select one:
- True
- False
answer is ( false ) and the correct is
Overvoltage in an alternator occurs when speed of the prime-mover increase due to sudden loss of the alternator load
50. If the three phase induction motor connected to a power grid with 3-star connected capacitors draws a real positive power (P) and zero reactive power (Q). If the capacitors is reconnected to run with delta-capacitors, then the motor will draw .............. (P) and ......... (Q).
- a. negative, negative
- b. positive, positive
- c. negative, positive
- d. positive, negative
51. The magnitude of the unprotected zone of the generator stator winding depends upon the value of earthing resistance and relay setting. Select one:
- True
- False
- True
- False
- i. A, B, D
- ii. A, B, C, D
- iii. B, C, D
- iv. A only
- v. D only
54. For 3-phase induction motor, the characteristic of motor the torque .................with respect to slip.
- a. decreases then increase
- b. increases
- c. decreases
- d. increases then decrease
- e. remains constant
55. The field of each individual phase inJotating machines is........ .
- a. not a rotating RMF but its amplitude pulsates
- b. not a rotating RMF and its amplitude doesn't alternate
- c. None of the mentioned
- d. a rotating magnetic filed RMF
56. If the stator winding fault is cleared quickly, it may lead to-------
- None of these
- ii. burning of stator coils
- iii. burning and welding-up of stator laminations
- iv. minimize the extent of damage
57. The consequences of a sudden loss of all or the major part of the load on the alternator -
- i. Failure of the field
- ii. None of these
- iii. Failure of the prime-mover
- iv. Overcurrent
- v. Overspeed
58. The reverse power relay is used for.........
- i. Failure of the prime-mover
- ii. Overcurrent
- iii. Overspeed
- iv. None of these
- v. Failure of the field
59. At standstill the equivalent of the 3-phase induction motor is similar to
- a. none of the mentioned
- b. short-circuited two winding transformer
- c. stand still synchronous motor
- d. open circuit two winding transformer
60. Full voltage startingof induction motor may cause Not yet answered
- a. high voltage Marked out of
- b. all of the mentioned 0.50
- c. high losses
- d. dip in the voltages
61. 3-phase, 10 MVA, 6.2 kV alternator is protected by Merz Price circulating-current principle if the minimum fault current is 110A. The E.M.F induced in x% winding is (35.8x) volts. Select one:
- True
- False
- a. star or delta connected
- b. delta connected
- c. star and delta connected
- d. star connected
63. For 3-phase induction motor, as load increases from no load towards the full load,
- a. efficiency remains same
- b. efficiency improves
- c. efficiency varies linearly
- d. efficiency increases till about 80% load and then decreases
64. A star-connected, 3-phase, 10 MVA, 6.6 kV alternator is protected by circulating current protection, the star point being earthed via a resistance (r). If 80% of the stator winding is protected against earth faults. Assume an earth fault setting of 20% of full-load current, and neglect the impedance of the alternator winding. Then the value of the earthing resistor is 9
- i. 4.355
- ii. 3.266
- i. 2.175
- iv. 5.125
- v. None of these
65. If the three phase induction motor connected to a power grid with 3-delta connected capacitors draws a real positive power (P) and zero reactive power (Q). If the capacitors is reconnected to run with star-capacitors, then the motor will draw
- a. (-P), (-Q)
- b. (P), (-Q)
- c. (-P), (Q)
- d. (P), (Q)
66. During the blocked rotor test the wattmeter reading will be: (( I. stator copper loss , II. stator core loss, II. rotor core loss , IV. friction and windage losses, V. Rotor copper loss ))
- a. 1, III, II, IV
- b. II,III, IV
- c. I, V
- d. II, IV
67. The magnitude of the unprotected zone of the generator stator winding depends upon the value of earthing resistance and relay setting. Select one:
- True
- False
68. The calculated apparent impedance is compared with the reach point impedance. If the measured impedance is higher than the reach point impedance, it is assumed that a fault exists on the line between the relay and the reach point. Select one:
- True
- False
69. Buchholz relay is a gas-actuated relay installed in oil-immersed transformers for protection against all kinds of earth-faults. tot Select one:
- True
- False
70. In the Definite-Time Relays, the time of operation of each relay is fixed and is independent operating current. Select one:
- True
- False
71. A 3-phase transformer of 220/11.5kV line volts is connected in star/delta. The protective transformers on the 220 V side have a current ratio of 600/5. What should be the CT ratio on 11.5kV side?
- i. 1.325 :1
- ii. 1.155 :1
- i. None of these
- iv. 1.449 :1
- v. 1.385 :1
72. Overvoltage in an alternator occurs when speed of the prime-mover decreases due to sudden loss of the alternator load. Select one:
- True
- False
answer is (false) and the correct is : Overvoltage in an alternator occurs when speed of the prime-mover increases due to sudden loss of the alternator load
- True
- False
74. Protection against earth-faults in a transformer is Known as the core-balance leakage protection. Select one:
- True
- False
75. Overvoltage in an alternator oceurs when speed of the prime-mover decreases due to sudden loss of the alternator load. Select one:
- True
- False
76. Time-ordered protection of a radial feeder can be achieved by using (i) definite time relays and (ii) inverse time relays. Select one:
- True
- False
77. Overvoltage in an alternator occurs when speed of the prime-mover decreases due to sudden loss of the alternator load. Select one:
- True
- False
78. If the neutral point of a star-connected the alternator is earthed through a sufficient sensitivity for earth-faults. Select one:
- True
- False
79. Overvoltage in an alternator occurs when speed of the prime-mover decreases due to sudden loss of the alternator load. utof Select one:
- True
- False
80. Unbalanced loading arises when a fault is
- i. All of these
- ii. Faults between phases and ground
- iii. Faults to earth
- iv. Three-phase faults
- v. None of these
- vi. Faults between phases
81. Overvoltage in an alternator occurs when speed of the prime-mover decreases due to sudden loss of the alternator load. Select one:
- True
- False
82. In the Merz-Price circulating scheme, the secondaries of each set of current transformers are connected in delta. Select one:
- True
- False
83. Overvoltage in an alternator occurs when speed of the prime-mover decreases due to sudden loss of the alternator load. of Select one:
- True
- False
84. If the neutral point of a star-connected the alternator is earthed through a low resistance, protection schemes will not provide sufficient sensitivity for earth-faults. of Select one:
- True
- False
Answer is (false) and the correct is : If the neutral point of a star-connected the alternator is earthed through a high resistance, protection schemes will not provide sufficient sensitivity for earth-faults
85. 3-phase, 10 MVA, 6.6 kV alternator is protected by Merz Price circulating-current principle if the minimum fault current is 100A The EMF induced in x% winding is (39.1x) volts
Select one:
86. 3-phase, 10 MVA, 6.6 kV alternator is protected by Merz Price circulating-current principle if the minimum fault current is 100A. The E.M.F induced in x% winding is (39.1x) volts. Select one:
87. Time-ordered protection of a radial feeder can be achieved by using (i) definite time relays and (ii) inverse time relays. Select one:
88. A 3-phase transformer of 220/11.5kV line volts is connected in star/delta. The protective transformers on the 220 V side have a current ratio of 600/5. What should be the CT ratio on 11.5kV side?
- True
- False
Answer is (false) and the correct is : 3-phase, 10 MVA, 6.6 kV alternator is protected by Merz Price circulating-current principle if the minimum fault current is 100A The EMF induced in x% winding is (38.1x) volts.
- True
- False
- True
- False
88. A 3-phase transformer of 220/11.5kV line volts is connected in star/delta. The protective transformers on the 220 V side have a current ratio of 600/5. What should be the CT ratio on 11.5kV side?
- i. None of these
- ii. 1.325:1
- iii. 1.155:1
- iv. 1.449 : 1
- V. 1.385 :1
89. For a delta/star power transformer, the CTs on the delta-side must be connected in delta and those on the star-side in the delta.Select one:
- True
- False
90. Field failure of alternators needs to automatic protection against this contingency Select one:
- True
- False
91. The basic principle of distance protection involves the division of the voltage at the relaying point by the measured current Select one:
- True
- False
More Electrical Machine MCQ to practice
A star-connected, 3-phase, 10 MVA, 6.2 kV alternator is protected by circulating current protection, the star point being earthed via a resistance (r). If 80% of the stator winding is protected against earth faults. Assume an earth fault setting of 15% of full-load current, and neglect the impedance of the alternator winding. Then the value of the earthing resistor is ----------- Ω
- i. 3.844
- ii. 5.125
- iii. 2.175
- iv. None of these
- v. 4.355
For 3-phase induction motor, the characteristic of motor the torque _______ with respect to slip.
- a. increases then decrease
- b. decreases
- c. remains constant
- d. increases
- e. decreases then increase
answer is (a)increses then decrease because its exponnetial
other sources that will help you in electrical mahine with mcq:
- https://mahtoamit.com/mcq-on-electrical-machine/
- https://www.sanfoundry.com/electrical-machines-questions-answers-aptitude-test/
Related Article
- 3 phase induction motor MCQ
- mcq | انسانيات - اخلاق المهنة في العصر الحديث -حقوق الانسان
- MCQ on Building Controls II: Control Sensors | Primo ...
- MCQ on Building Controls I: An Introduction to Building ...
- MCQ on Active Energy Efficiency Using Speed Control ...
- MCQ on Boiler Types and Opportunities for Energy ...
- MCQ on Building Controls IV: Two Position and Floating ...
- MCQ on HVAC Thermodynamic States | ENERGY ..